ADTRAN-TA5000-THERMAL-MGMT-MIB  DEFINITIONS ::= BEGIN

    -- TITLE:       TA5000 Thermal Management MIB
    -- FILENAME:    adta5kthermalmgmt.mi2
    -- PARTNUMBER:  Multiple
    -- AUTHOR:      Geoff Oltmans
    -- DATE:        07/10/2013
    --
    -- This MIB defines the TA5000 thermal management support, including but not limited to
    -- alarming for high temperature conditions, and retrieval of temperature data.

        IMPORTS
           MODULE-IDENTITY,
           OBJECT-TYPE,
           NOTIFICATION-TYPE,
           Integer32
                  FROM SNMPv2-SMI
           sysName
                  FROM SNMPv2-MIB
           DisplayString,
           TruthValue
                  FROM SNMPv2-TC
           adIdentity,
           adProducts,
           adMgmt
                  FROM ADTRAN-MIB
           ifIndex
                  FROM IF-MIB
                  
           adTa5kThermalManagement,
   	       adTa5kThermalManagementID
            	  FROM ADTRAN-GENTA5K-MIB
           adGenSlotInfoIndex
                  FROM ADTRAN-GENSLOT-MIB
           adTrapInformSeqNum
                  FROM ADTRAN-GENTRAPINFORM-MIB
           ;

    adTa5kThermalMgmtModuleIdentity MODULE-IDENTITY
        LAST-UPDATED "201311250000Z"
        ORGANIZATION
            "ADTRAN, Inc."
        CONTACT-INFO
            "CND Tech Support
                Postal: ADTRAN, Inc.
                        901 Explorer Blvd.
                        Huntsville, AL  35806
                        Tel: +1 800 726-8663
                        Fax: +1 256 963 6217
                        E-mail: support@adtran.com"
        DESCRIPTION
            "Total Access 5000 Thermal Management MIB"

        REVISION "201311250000Z"
        DESCRIPTION "Added adTa5kRemoteDeviceCriticalTempActive
                     and adTa5kRemoteDeviceCriticalTempClear."

        REVISION "201308012100Z"
        DESCRIPTION "Initial"
             
        ::= { adTa5kThermalManagementID 1 }

    -- OBJECT IDENTIFIERS

    adTA5kThermalMgmtmg      OBJECT IDENTIFIER ::= { adTa5kThermalManagement 1 }
    adTA5kThermalEventsFix   OBJECT IDENTIFIER ::= { adTa5kThermalManagement 2 }

    adTa5kThermalEvents      OBJECT IDENTIFIER ::= { adTA5kThermalEventsFix 0 }
    adTA5kThermal            OBJECT IDENTIFIER ::= { adTA5kThermalMgmtmg 1 }


-- ============================================================================


-- ============================================================================
-- TA5000 Thermal Management Slot Table
-- ============================================================================

   adTA5kThermalSlotTable OBJECT-TYPE
       SYNTAX      SEQUENCE OF AdTA5kThermalSlotEntry
       MAX-ACCESS  not-accessible
       STATUS      current
       DESCRIPTION
               "Table of slot indexed OIDs to support this MIB."
       ::= { adTA5kThermal 1 }

   adTA5kThermalSlotEntry OBJECT-TYPE
       SYNTAX      AdTA5kThermalSlotEntry
       MAX-ACCESS  not-accessible
       STATUS      current
       DESCRIPTION
               "An entry in the Thermal Slot Table. This table
                is indexed by adGenSlotInfoIndex."
       INDEX   { adGenSlotInfoIndex }
       ::= { adTA5kThermalSlotTable 1 }

   AdTA5kThermalSlotEntry ::=
       SEQUENCE {
           adTA5kThermalSlotNumSensors
               Integer32
       }

    adTA5kThermalSlotNumSensors  OBJECT-TYPE
        SYNTAX      Integer32
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of sensors that are accessible on this slot."
        ::= { adTA5kThermalSlotEntry 1 }


-- ============================================================================
-- TA5000 Thermal Management Slot/Sensor Table
-- ============================================================================

   adTA5kThermalManagementTable OBJECT-TYPE
       SYNTAX      SEQUENCE OF AdTA5kThermalManagementEntry
       MAX-ACCESS  not-accessible
       STATUS      current
       DESCRIPTION
               "Table of OIDs indexed by slot and temp sensor id."
       ::= { adTA5kThermal 2 }

   adTA5kThermalManagementEntry OBJECT-TYPE
       SYNTAX      AdTA5kThermalManagementEntry
       MAX-ACCESS  not-accessible
       STATUS      current
       DESCRIPTION
               "An entry in the Thermal Management Table. This table
                is indexed by adGenSlotInfoIndex and adTA5kThermalManagementSensorId."
       INDEX   { adGenSlotInfoIndex, adTA5kThermalManagementSensorId }
       ::= { adTA5kThermalManagementTable 1 }

   AdTA5kThermalManagementEntry ::=
       SEQUENCE {
           adTA5kThermalManagementSensorId
               Integer32,
           adTA5kThermalManagementSensorName
               DisplayString,
           adTA5kThermalManagementSensorCurrTemp
               Integer32
       }

    adTA5kThermalManagementSensorId  OBJECT-TYPE
        SYNTAX      Integer32
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "ID of the sensor."
        ::= { adTA5kThermalManagementEntry 1 }

    adTA5kThermalManagementSensorName  OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The Human-readable name for this temperature sensor."
        ::= { adTA5kThermalManagementEntry 2 }

    adTA5kThermalManagementSensorCurrTemp  OBJECT-TYPE
        SYNTAX      Integer32
        UNITS		"0.1C"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The current temperature reported by this temperature sensor,
             in tenths of a degree celsius."
        ::= { adTA5kThermalManagementEntry 3 }

-- ============================================================================
-- TA5000 Thermal Traps
-- ============================================================================

adTA5kSlotCriticalTempActive  NOTIFICATION-TYPE
        OBJECTS {
                adTrapInformSeqNum,
                sysName,
                adGenSlotInfoIndex,
                adTA5kThermalManagementSensorCurrTemp
        }  
        STATUS current
        DESCRIPTION
                "This trap indicates that the critical temperature threshold for the
                 card has been reached. Indicates whether or not equipment is in danger
                 of shutting down, shedding power, or otherwise due to a critical high 
                 temperature condition. The equipment will take appropriate actions to 
                 protect the hardware from damage."

        --#TYPE       "Error - Critical Temperature Alarm Active"
        --#SUMMARY    "TA5000 Slot: Critical Temperature Alarm active for "
        --#SUMMARY    "Shelf %s, Slot %d"
        --#ARGUMENTS  {1, 2}
        --#SEVERITY   CRITICAL
        --#GENERIC    6
        --#CATEGORY   "Error Events"
        --#SOURCE_ID  "A"
        --#TIMEINDEX  0
        ::= { adTa5kThermalEvents 1 }

adTA5kSlotCriticalTempClear  NOTIFICATION-TYPE
        OBJECTS {
                adTrapInformSeqNum,
                sysName,
                adGenSlotInfoIndex,
                adTA5kThermalManagementSensorCurrTemp
        }
        STATUS current
        DESCRIPTION
                "This trap indicates that the critical temperature condition previously
                 declared for this card has now cleared."
        --#TYPE       "Error - Critical Temperature Alarm Cleared"
        --#SUMMARY    "TA5000 Slot: Critical Temperature Alarm cleared for "
        --#SUMMARY    "Shelf %s, Slot %d"
        --#ARGUMENTS  {1, 2}
        --#SEVERITY   CRITICAL
        --#GENERIC    6
        --#CATEGORY   "Error Events"
        --#SOURCE_ID  "A"
        --#TIMEINDEX  0
        ::= { adTa5kThermalEvents 2 }
        
adTa5kRemoteDeviceCriticalTempActive  NOTIFICATION-TYPE
        OBJECTS {
                adTrapInformSeqNum,
                sysName,
                ifIndex
        }  
        STATUS current
        DESCRIPTION
                "This trap indicates that the critical temperature threshold for the
                 remote device has been reached. Indicates whether or not equipment is
                 in danger of shutting down, shedding power, or otherwise due to a
                 critical high temperature condition. The equipment will take
                 appropriate actions to protect the hardware from damage."

        --#TYPE       "Error - Critical Temperature Alarm Active"
        --#SUMMARY    "TA5000 Device: Critical Temperature Alarm active for "
        --#SUMMARY    "Shelf %s, Device %d"
        --#ARGUMENTS  {1, 2}
        --#SEVERITY   CRITICAL
        --#GENERIC    6
        --#CATEGORY   "Error Events"
        --#SOURCE_ID  "A"
        --#TIMEINDEX  0
        ::= { adTa5kThermalEvents 3 }

adTa5kRemoteDeviceCriticalTempClear  NOTIFICATION-TYPE
        OBJECTS {
                adTrapInformSeqNum,
                sysName,
                ifIndex
        }
        STATUS current
        DESCRIPTION
                "This trap indicates that the critical temperature condition previously
                 declared for this device has now cleared."
        --#TYPE       "Error - Critical Temperature Alarm Cleared"
        --#SUMMARY    "TA5000 Device: Critical Temperature Alarm cleared for "
        --#SUMMARY    "Shelf %s, Device %d"
        --#ARGUMENTS  {1, 2}
        --#SEVERITY   CRITICAL
        --#GENERIC    6
        --#CATEGORY   "Error Events"
        --#SOURCE_ID  "A"
        --#TIMEINDEX  0
        ::= { adTa5kThermalEvents 4 }

END