-- MIB version: 1.1.104

-- MIB release note
--        |    date     | MIB version |   note
---------------------------------------------------------------------------------------------------
--        | 2018/02/13  | 1.1.101     |   Initial version
---------------------------------------------------------------------------------------------------
--        | 2018/03/01  | 1.1.102     |   Modify descriptions of bankStatusRatedCur, outletStatusRatedCur, and outletStatusSwitchable
---------------------------------------------------------------------------------------------------
--        | 2019/09/09  | 1.1.103     |   Add staStatusHasAutoPing, outletStatusAutoPing, outletConfigAutoPing. Modify sensorConfigTable, sensorReadingTable to support port-address indexing
---------------------------------------------------------------------------------------------------
--        | 2019/10/08  | 1.1.104     |   Add trapNotification. Add netConfigTable to support port indexing for dual-network
---------------------------------------------------------------------------------------------------
--        | 2020/11/23  | 1.1.105     |   Add deviceLock to change password of SNMP for California passes law
---------------------------------------------------------------------------------------------------
--        | 2021/05/06  | 1.1.106     |   Add phase layout of outlet and bank
---------------------------------------------------------------------------------------------------
--        | 2021/08/24  | 1.1.107     |   Add inlet entry and inlet number
---------------------------------------------------------------------------------------------------
--        | 2021/10/01  | 1.1.108     |   Add smoke sensor in dry contact
---------------------------------------------------------------------------------------------------
--        | 2021/11/02  | 1.1.109     |   Add InetAddress and InetAddressType for support ipv4/ipv6
---------------------------------------------------------------------------------------------------

-- ATEN International Co., Ltd.
-- This file defines the mib struct of Management in PE series
-- We attach this mib node on enterprises.aten.atenProducts.overip.poweroverip.pe2 subtree
                                                  
ATEN-PE2-CFG DEFINITIONS ::= BEGIN
    IMPORTS
        enterprises, IpAddress, Gauge, TimeTicks     FROM RFC1155-SMI
        DisplayString                                FROM RFC1213-MIB
        OBJECT-TYPE                                  FROM RFC-1212
        TRAP-TYPE                                    FROM RFC-1215
        MODULE-IDENTITY, NOTIFICATION-TYPE           FROM SNMPv2-SMI
        KeyChange                                    FROM SNMP-USER-BASED-SM-MIB
        MacAddress                                   FROM SNMPv2-TC
        poweroverip                                  FROM ATEN-PRODUCTS-MIB
		InetAddressType, InetAddress, InetPortNumber FROM INET-ADDRESS-MIB;

    pe2  MODULE-IDENTITY
         LAST-UPDATED "201801231200Z"
         ORGANIZATION "ATEN"
         CONTACT-INFO "Aten, Inc."
         DESCRIPTION  "ATEN PE MIB"
         REVISION     "201801231200Z"
         DESCRIPTION  "support stations"
         ::= { poweroverip 3 }

    management            OBJECT IDENTIFIER ::= { pe2 1 }
    energy                OBJECT IDENTIFIER ::= { pe2 2 }
        device            OBJECT IDENTIFIER ::= { energy 1 }
        bank              OBJECT IDENTIFIER ::= { energy 2 }
        outlet            OBJECT IDENTIFIER ::= { energy 3 }
        line              OBJECT IDENTIFIER ::= { energy 4 }
		inlet			  OBJECT IDENTIFIER ::= { energy 5 }
    environment           OBJECT IDENTIFIER ::= { pe2 3 }
        sensor            OBJECT IDENTIFIER ::= { environment 1 }
        dryContact        OBJECT IDENTIFIER ::= { environment 2 }
    network               OBJECT IDENTIFIER ::= { pe2 4 }
    event                 OBJECT IDENTIFIER ::= { pe2 5 }
        trap              OBJECT IDENTIFIER ::= { event 1 }
    trapNotification      OBJECT IDENTIFIER ::= { pe2 50 }
	deviceLock      	  OBJECT IDENTIFIER ::= { pe2 150 }
---------------------------------------------------------------------------------------------------
-- Management
---------------------------------------------------------------------------------------------------
staCount OBJECT-TYPE
    SYNTAX INTEGER (1..16)
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "The available station count which includes master and slave stations."
    ::= { management 1 }

staStatusTable OBJECT-TYPE
    SYNTAX SEQUENCE OF StaStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Station status table."
    ::= { management 2 }

staStatusEntry OBJECT-TYPE
    SYNTAX StaStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing station status info."
    INDEX { staId }
    ::= { staStatusTable 1 }
     
StaStatusEntry ::=
    SEQUENCE {
        staId                   INTEGER,
        staStatusFWVer          DisplayString,
        staStatusModelName      DisplayString,
        staStatusSwitchable     INTEGER,
        staStatusPerPortReading INTEGER,
        staStatusBankCount      INTEGER,
        staStatusOutletCount    INTEGER,
        staStatusSensorCount    INTEGER,
        staStatusHasAutoPing    INTEGER,
		staStatusInletCount		INTEGER
    }

staId OBJECT-TYPE
    SYNTAX INTEGER (1..16)
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Station ID."
    ::= { staStatusEntry 1 }

staStatusFWVer OBJECT-TYPE
    SYNTAX DisplayString
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Station FW version.
        If the station is not available, it returns 'station N/A'."
    ::= { staStatusEntry 2 }

staStatusModelName OBJECT-TYPE
    SYNTAX DisplayString
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Station model name.
        If the station is not available, it returns 'station N/A'"
    ::= { staStatusEntry 3 }

staStatusSwitchable OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), mix(3) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Outlets of the station are switchable or not.
        If the station is not available, it returns value -3000000."
    ::= { staStatusEntry 4 }

staStatusPerPortReading OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Outlets of the station are per-port reading or not.
        If the station is not available, it returns value -3000000."
    ::= { staStatusEntry 5 } 

staStatusBankCount OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Station bank count.
        If the station is not available, it returns value -3000000."
    ::= { staStatusEntry 6 }

staStatusOutletCount OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Station outlet count.
        If the station is not available, it returns value -3000000."
    ::= { staStatusEntry 7 }

staStatusSensorCount OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Station sensor count.
        If the station is not available, it returns value -3000000."
    ::= { staStatusEntry 8 }

staStatusHasAutoPing OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "The station supports auto-ping or not.
        If the station is not available, it returns value -3000000."
    ::= { staStatusEntry 9 }
	
staStatusInletCount OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Station inlet count.
        If the station is not available, it returns value -3000000."
    ::= { staStatusEntry 10 }

---------------------------------------------------------------------------------------------------
-- staControlTable
---------------------------------------------------------------------------------------------------
staControlTable OBJECT-TYPE
    SYNTAX SEQUENCE OF StaControlEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Station control table."
    ::= { management 3 }

staControlEntry OBJECT-TYPE
    SYNTAX StaControlEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing station control info."
    INDEX { staId }
    ::= { staControlTable 1 }
     
StaControlEntry ::=
    SEQUENCE {
        staControlReboot
       INTEGER
    }

staControlReboot OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(4) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Reboot the station.
        If the station is not available, it returns value -3000000."
    ::= { staControlEntry 1 } 

---------------------------------------------------------------------------------------------------
-- rackConfigTable
---------------------------------------------------------------------------------------------------
rackConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF RackConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Rack config table."
    ::= { management 4 }

rackConfigEntry OBJECT-TYPE
    SYNTAX RackConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing rack config info."
    INDEX { staId }
    ::= { rackConfigTable 1 }
     
RackConfigEntry ::=
    SEQUENCE {
        rackConfigName   DisplayString,
        rackConfigRow    INTEGER,
        rackConfigColumn INTEGER
    }

rackConfigName OBJECT-TYPE
    SYNTAX DisplayString
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set station's rack name.
        string length: 1~32
        If the station is not available, it returns 'station N/A'.
        NOTE: Input string as /empty to set this object to NULL."
    ::= { rackConfigEntry 1 } 

rackConfigRow OBJECT-TYPE
    SYNTAX INTEGER (1..26)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set station's rack row number.
        If the station is not available, it returns value -3000000."
    ::= { rackConfigEntry 2 }

rackConfigColumn OBJECT-TYPE
    SYNTAX INTEGER (1..26)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set station's rack column number.
        If the station is not available, it returns value -3000000."
    ::= { rackConfigEntry 3 }

staState OBJECT-TYPE
    SYNTAX DisplayString
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Cascade stations' state. Return string length equals to the MAX support stations.
        If station N is alive, display 1 at the N's character, else, display 0.
        The first character is always 1 as it belongs to the Master."
    ::= { management 5 }

---------------------------------------------------------------------------------------------------
-- devStatusTable
---------------------------------------------------------------------------------------------------
devStatusTable OBJECT-TYPE
    SYNTAX SEQUENCE OF DevStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Device status table."
    ::= { device 1 }

devStatusEntry OBJECT-TYPE
    SYNTAX DevStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing device status info."
    INDEX { staId }
    ::= { devStatusTable 1 }
     
DevStatusEntry ::=
    SEQUENCE {
        devStatusRatedCur   INTEGER,
        devStatusRatedVol   INTEGER,
        devStatusRatedPower INTEGER,
		devStatusWiredType	INTEGER
    }

devStatusRatedCur OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Device input Current value. unit:(0.1mA)
        If the station does not support this OID, we show value 0.
        If the station is not available, it returns value -3000000."
    ::= { devStatusEntry 1 }

devStatusRatedVol OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Device input Voltage value. unit:(0.1mV)    
        If the station does not support this OID, we show value 0.
        If the station is not available, it returns value -3000000."
    ::= { devStatusEntry 2 }

devStatusRatedPower OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Device power Capacity value. unit:(0.1mVA)
        If the station does not support this OID, we show value 0.
        If the station is not available, it returns value -3000000."
    ::= { devStatusEntry 3 }
	
devStatusWiredType OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Device circuit wired type
		Example: 1 for 1 phase, 2 for 3 phase wye, 3 for 3 phase delta
        If the station does not support this OID, we show value 0.
        If the station is not available, it returns value -3000000."
    ::= { devStatusEntry 4 }

---------------------------------------------------------------------------------------------------
-- devConfigTable
---------------------------------------------------------------------------------------------------
devConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF DevConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Device config table."
    ::= { device 2 }

devConfigEntry OBJECT-TYPE
    SYNTAX DevConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing device config info."
    INDEX { staId }
    ::= { devConfigTable 1 }
     
DevConfigEntry ::=
    SEQUENCE {
        devConfigDevName                   DisplayString,
        devConfigPowerOnScheduleEn         INTEGER,
        devConfigOutletsSequentialRebootEn INTEGER,
        devConfigMinCurThresh              INTEGER,
        devConfigMaxCurThresh              INTEGER,
        devConfigMinVolThresh              INTEGER,
        devConfigMaxVolThresh              INTEGER,
        devConfigMinPowerThresh            INTEGER,
        devConfigMaxPowerThresh            INTEGER,
        devConfigMaxPDThresh               INTEGER
    }

devConfigDevName OBJECT-TYPE
    SYNTAX DisplayString
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "The name of the device.
        string length: 1~39
        If the station is not available, it returns 'station N/A'.
        NOTE: Input string as /empty to set this object to NULL."
    ::= { devConfigEntry 1 } 

devConfigPowerOnScheduleEn OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no-delaytime(1), delaytime(2), not-support(3) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set whether power on schedule or not.
        If the station is not available, it returns value -3000000."
    ::= { devConfigEntry 2 }

devConfigOutletsSequentialRebootEn OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(3) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "This function is used to enable or disable all outlet ports to sequential reboot.
        If the station is not available, it returns value -3000000."
    ::= { devConfigEntry 3 }

devConfigMinCurThresh OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set device minimum electric current measurement threshold.
        Example: range 0.0~32.0 represents 0~320.
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { devConfigEntry 4 }

devConfigMaxCurThresh OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set device maximum electric current measurement threshold.  
        Example: range 0.0~32.0 represents 0~320
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { devConfigEntry 5 }

devConfigMinVolThresh OBJECT-TYPE
    SYNTAX INTEGER (-3000 | 900..2600)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set device minimum voltage measurement threshold. 
        Example: range 90.0~260.0 represents 900~2600
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { devConfigEntry 6 }

devConfigMaxVolThresh OBJECT-TYPE
    SYNTAX INTEGER (-3000 | 900..2600)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set device maximum voltage measurement threshold. 
        Example: range 90.0~260.0 represents 900~2600
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { devConfigEntry 7 }

devConfigMinPowerThresh OBJECT-TYPE
    SYNTAX INTEGER (-3000 | 0..99999)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set device minimum power measurement threshold. 
        Example: range 0.0 ~ 9999.9 represents 0~99999
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { devConfigEntry 8 }

devConfigMaxPowerThresh OBJECT-TYPE
    SYNTAX INTEGER (-3000 | 0..99999)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set device maximum power measurement threshold. 
        Example: range 0.0 ~ 9999.9 represents 0~99999
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { devConfigEntry 9 }

devConfigMaxPDThresh OBJECT-TYPE
    SYNTAX INTEGER (-3000 | 0..999990)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set device maximum power dissipation measurement threshold. 
        Example: range 0.0 ~ 99999.0 represents 0~999990
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { devConfigEntry 10 }

---------------------------------------------------------------------------------------------------
-- devControlTable
---------------------------------------------------------------------------------------------------
devControlTable OBJECT-TYPE
    SYNTAX SEQUENCE OF DevControlEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Device control table."
    ::= { device 3 }

devControlEntry OBJECT-TYPE
    SYNTAX DevControlEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing device control info."
    INDEX { staId }
    ::= { devControlTable 1 }
     
DevControlEntry ::=
    SEQUENCE {
        devControlOperation
       INTEGER
    }

devControlOperation OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), off(1), on(2), reboot(3), nostatus(4), not-support(5) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "This function is used for outlet control of device.
         Set off(1) to turn off for outlet control of device.
         Set on(2) to turn on for all outlet control of device.
         Set reboot(3) to reboot for outlet control of device.
         Get this object always return nostatus(3), because there is no device status.
         If the station is not available, it returns value -3000000."
    ::= { devControlEntry 1 }

---------------------------------------------------------------------------------------------------
-- devReadingTable
---------------------------------------------------------------------------------------------------
devReadingTable OBJECT-TYPE
    SYNTAX SEQUENCE OF DevReadingEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Device reading table."
    ::= { device 4 }

devReadingEntry OBJECT-TYPE
    SYNTAX DevReadingEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing device reading info."
    INDEX { staId }
    ::= { devReadingTable 1 }
     
DevReadingEntry ::=
    SEQUENCE {
        devReadingCur   INTEGER,
        devReadingVol   INTEGER,
        devReadingPower INTEGER,
        devReadingPD    INTEGER,
        devReadingPF    INTEGER
    }

devReadingCur OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Device electric current value.
        This value indicates that 10,000 times.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { devReadingEntry 1 } 

 devReadingVol OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Device voltage value.
        This value indicates that 10,000 times.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { devReadingEntry 2 }    

devReadingPower OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Device power value.
        This value indicates that 10,000 times.  
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { devReadingEntry 3 }

devReadingPD OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Device power dissipation value.
        This value indicates that 10,000 times.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { devReadingEntry 4 }

devReadingPF OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Device power factor value.
        This value indicates that 100 times.  
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { devReadingEntry 5 }

---------------------------------------------------------------------------------------------------
-- popConfigTable
---------------------------------------------------------------------------------------------------
popConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF PopConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "POP config table."
    ::= { device 5 }

popConfigEntry OBJECT-TYPE
    SYNTAX PopConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing POP config info."
    INDEX { staId }
    ::= { popConfigTable 1 }
     
PopConfigEntry ::=
    SEQUENCE {
        popConfigOutletModeEn   INTEGER,
        popConfigLIFOModeEn     INTEGER,
        popConfigPriorityModeEn INTEGER,
        popConfigPriorityList   DisplayString
    }

popConfigOutletModeEn OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(3) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set whether outlet POP mode is enabled or not.
        If the station is not available, it returns value -3000000."
    ::= { popConfigEntry 1 }

popConfigLIFOModeEn OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(3) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set whether LIFO POP mode is enabled or not.
        If the station is not available, it returns value -3000000."
    ::= { popConfigEntry 2 }

popConfigPriorityModeEn OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2), not-support(3) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set whether priority POP mode is enabled or not.
        If the station is not available, it returns value -3000000."
    ::= { popConfigEntry 3 }

popConfigPriorityList OBJECT-TYPE
    SYNTAX DisplayString
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Indicate Outlets' power OFF priorities under Priority POP mode.
        Outlet Separator ','
        Bank Separator '#'
        Assign each priority in each bank by Outlet index or zero (indicate N/A) with separators in ascendant order.
        e.g. for model PE8324 ( Bank1: outlet 1 ~ 16, Bank2: outlet 17 ~ 24 ) 
        If you want to assign priority 2, 5 of Bank 1 with Outlet 14, 3, 
        and priority 2, 6, 8 with of Bank 2 with Outlet 17, 23, 24 and left the rest with N/A,
        please type: 0,14,0,0,3,0,0,0,0,0,0,0,0,0,0,0#0,17,0,0,0,23,0,24.
        If the station is not available, it returns 'station N/A'."
    ::= { popConfigEntry 4 } 

---------------------------------------------------------------------------------------------------
-- capConfigTable
---------------------------------------------------------------------------------------------------
capConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF CapConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "CAP config table."
    ::= { device 6 }

capConfigEntry OBJECT-TYPE
    SYNTAX CapConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing CAP config info."
    INDEX { staId, outletId }
    ::= { capConfigTable 1 }
     
CapConfigEntry ::=
    SEQUENCE {
        capConfigModeEn INTEGER
    }
    
capConfigModeEn OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set whether CAP mode is enabled or not.
        If the station is not available, it returns value -3000000."
    ::= { capConfigEntry 1 } 

---------------------------------------------------------------------------------------------------
-- capPriorityConfigTable
---------------------------------------------------------------------------------------------------
capPriorityConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF CapPriorityConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "CAP priority config table."
    ::= { device 7 }

capPriorityConfigEntry OBJECT-TYPE
    SYNTAX CapPriorityConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing CAP priority config info."
    INDEX { staId, outletId }
    ::= { capPriorityConfigTable 1 }
     
CapPriorityConfigEntry ::=
    SEQUENCE {
        capPriorityConfigOutlet INTEGER
    }
    
capPriorityConfigOutlet OBJECT-TYPE
    SYNTAX INTEGER (0..99)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the CAP Priority of outlet.
        Priority 0 means this outlet does not support this OID.
        If the station is not available, it returns value -3000000."
    ::= { capPriorityConfigEntry 1 }

---------------------------------------------------------------------------------------------------
-- bankStatusTable
---------------------------------------------------------------------------------------------------
bankStatusTable OBJECT-TYPE
    SYNTAX SEQUENCE OF BankStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Bank status table."
    ::= { bank 1 }

bankStatusEntry OBJECT-TYPE
    SYNTAX BankStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing bank status info."
    INDEX { staId, bankId }
    ::= { bankStatusTable 1 }
     
BankStatusEntry ::=
    SEQUENCE {
        bankId                  INTEGER,
        bankStatusRatedCur      INTEGER,
        bankStatusAttachStatus  INTEGER,
        bankStatusBreakerStatus INTEGER,
		bankStatusPhaseLayout	INTEGER
    }

bankId OBJECT-TYPE
    SYNTAX INTEGER (1..30)
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Bank ID."
    ::= { bankStatusEntry 1 }

bankStatusRatedCur OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "The Bank Max Current value. unit: (0.1mA).
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { bankStatusEntry 2 }

bankStatusAttachStatus OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), noattached(1), attached(2), error(3), noexisted(4) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "The bank attached status.
        If the station is not available, it returns value -3000000."
    ::= { bankStatusEntry 3 }

bankStatusBreakerStatus OBJECT-TYPE
   SYNTAX INTEGER { staNotAvailable(-3000000), off(1), on(2), not-support(3) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "The breaker status.
        If the station is not available, it returns value -3000000."
    ::= { bankStatusEntry 4 }
	
bankStatusPhaseLayout OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), l1-n(1), l2-n(2), l3-n(3), l1-l2(4), l2-l3(5), l3-l1(6) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Display the phase layout of bank.
        Example: range 1 ~ 3 represents Line1-LineNeutral ~ Line3-lineNeutral.
					   4 ~ 6 represents Line1-Line2, Line2-Line3, Line3-Line1.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { bankStatusEntry 5 }

---------------------------------------------------------------------------------------------------
-- bankConfigTable
---------------------------------------------------------------------------------------------------
bankConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF BankConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Bank config table."
    ::= { bank 2 }

bankConfigEntry OBJECT-TYPE
    SYNTAX BankConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing bank config info."
    INDEX { staId, bankId }
    ::= { bankConfigTable 1 }
     
BankConfigEntry ::=
    SEQUENCE {
        bankConfigName           DisplayString,
        bankConfigMinCurThresh   INTEGER,
        bankConfigMaxCurThresh   INTEGER,
        bankConfigMinVolThresh   INTEGER,
        bankConfigMaxVolThresh   INTEGER,
        bankConfigMinPowerThresh INTEGER,
        bankConfigMaxPowerThresh INTEGER,
        bankConfigMaxPDThresh    INTEGER
    }

bankConfigName OBJECT-TYPE
    SYNTAX DisplayString
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the name of the bank.
        When this model does not support the OID, we show n/a.
        string length: 0~15
        If the station is not available, it returns 'station N/A'.
        NOTE: Input string as /empty to set this object to NULL."
    ::= { bankConfigEntry 1 }

bankConfigMinCurThresh OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the bank minimum electric current measurement threshold. 
        Example: range 0.0 ~16.0 represents 0~160
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { bankConfigEntry 2 }

bankConfigMaxCurThresh OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the bank maximum electric current measurement threshold. 
        Example: range 0.0 ~16.0 represents 0~160
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { bankConfigEntry 3 }

bankConfigMinVolThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 900..2600)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the bank minimum voltage measurement threshold. 
        Example: range 90.0 ~260.0 represents 900~2600
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { bankConfigEntry 4 }

bankConfigMaxVolThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 900..2600)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the bank maximum voltage measurement threshold. 
        Example: range 90.0 ~260.0 represents 900~2600
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { bankConfigEntry 5 }

bankConfigMinPowerThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the bank minimum power measurement threshold.
        Example: range 0.0 ~ 9999.9 represents 0~99999
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { bankConfigEntry 6 }

bankConfigMaxPowerThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the bank maximum power measurement threshold.
        Example: range 0.0 ~ 9999.9 represents 0~99999
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { bankConfigEntry 7 }

bankConfigMaxPDThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..999990)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the bank maximum power dissipation measurement threshold.
        Example: range 0.0 ~ 99999.0 represents 0~999990
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { bankConfigEntry 8 }

---------------------------------------------------------------------------------------------------
-- bankControlTable
---------------------------------------------------------------------------------------------------
bankControlTable OBJECT-TYPE
    SYNTAX SEQUENCE OF BankControlEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Bank control table."
    ::= { bank 3 }

bankControlEntry OBJECT-TYPE
    SYNTAX BankControlEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing bank control info."
    INDEX { staId, bankId }
    ::= { bankControlTable 1 }
     
BankControlEntry ::=
    SEQUENCE {
        bankControlOperation
       INTEGER
    }

bankControlOperation OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), off(1), on(2), reboot(3), nostatus(4), not-support(5) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "This function is used for outlet control of bank.
        Set off(1) to turn off for outlet control of bank.
        Set on(2) to turn on for all outlet control of bank.
        Set reboot(3) to reboot for outlet control of bank.
        Get this object always return nostatus(3), because there is no bank status.
        If the station is not available, it returns value -3000000."
    ::= { bankControlEntry 1 }

---------------------------------------------------------------------------------------------------
-- bankReadingTable
---------------------------------------------------------------------------------------------------
bankReadingTable OBJECT-TYPE
    SYNTAX SEQUENCE OF BankReadingEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Bank reading table."
    ::= { bank 4 }

bankReadingEntry OBJECT-TYPE
    SYNTAX BankReadingEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing bank reading info."
    INDEX { staId, bankId }
    ::= { bankReadingTable 1 }
     
BankReadingEntry ::=
    SEQUENCE {
        bankReadingCur   INTEGER,
        bankReadingVol   INTEGER,
        bankReadingPower INTEGER,
        bankReadingPD    INTEGER,
        bankReadingPF    INTEGER
    }

bankReadingCur OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Bank electric current value.
        This value indicates that 10,000 times.
        If this measurement value is not available, it returns value -1000000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { bankReadingEntry 1 }

bankReadingVol OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Bank voltage value.
        This value indicates that 10,000 times.
        If this measurement value is not available, it returns value -1000000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { bankReadingEntry 2 }

bankReadingPower OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Bank power value.
        This value indicates that 10,000 times.
        If this measurement value is not available, it returns value -1000000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { bankReadingEntry 3 }   

bankReadingPD OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Bank power dissipation value.
        This value indicates that 10,000 times.
        If this measurement value is not available, it returns value -1000000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { bankReadingEntry 4 }

bankReadingPF OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Bank power Factor value.
        This value indicates that 100 times.  
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { bankReadingEntry 5 }

---------------------------------------------------------------------------------------------------
-- outletStatusTable
---------------------------------------------------------------------------------------------------
outletStatusTable OBJECT-TYPE
    SYNTAX SEQUENCE OF OutletStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Outlet status table."
    ::= { outlet 1 }

outletStatusEntry OBJECT-TYPE
    SYNTAX OutletStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing outlet status info."
    INDEX { staId, outletId }
    ::= { outletStatusTable 1 }
     
OutletStatusEntry ::=
    SEQUENCE {
        outletId               INTEGER,
        outletStatusRatedCur   INTEGER,
        outletStatusSwitchable INTEGER,
        outletStatusAutoPing   INTEGER,
		outletStatusPhaseLayout INTEGER
    }

outletId OBJECT-TYPE
    SYNTAX INTEGER (1..42)
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Outlet ID."
    ::= { outletStatusEntry 1 }

outletStatusRatedCur OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Outlet Max Current value. unit: (0.1mA).
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletStatusEntry 2 }

outletStatusSwitchable OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), no(1), yes(2) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Outlet switchable.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletStatusEntry 3 }

outletStatusAutoPing OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), na(1), online(2), not-reachable(3) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Outlet latest auto-ping result.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletStatusEntry 4 }
	
outletStatusPhaseLayout OBJECT-TYPE
	SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), l1-n(1), l2-n(2), l3-n(3), l1-l2(4), l2-l3(5), l3-l1(6) }
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Display the phase layout of outlet.
		Example: range 1 ~ 3 represents Line1-LineNeutral ~ Line3-lineNeutral.
					   4 ~ 6 represents Line1-Line2, Line2-Line3, Line3-Line1.
		If the station does not support this OID, it returns value -2000000.
		If the station is not available, it returns value -3000000."
	::= { outletStatusEntry 5 }

---------------------------------------------------------------------------------------------------
-- outletConfigTable
---------------------------------------------------------------------------------------------------
outletConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF OutletConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Outlet config table."
    ::= { outlet 2 }

outletConfigEntry OBJECT-TYPE
    SYNTAX OutletConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing outlet config info."
    INDEX { staId, outletId }
    ::= { outletConfigTable 1 }
     
OutletConfigEntry ::=
    SEQUENCE {
        outletConfigName               DisplayString,
        outletConfigConfirmationEn     INTEGER,
        outletConfigOnDelayTime        INTEGER,
        outletConfigOffDelayTime       INTEGER,
        outletConfigShutdownMethod     INTEGER,
        outletConfigMAC                MacAddress,
        outletConfigLocalAccessLock    INTEGER,
        outletConfigMinCurThresh       INTEGER,
        outletConfigMaxCurThresh       INTEGER,
        outletConfigMinVolThresh       INTEGER,
        outletConfigMaxVolThresh       INTEGER,
        outletConfigMinPowerThresh     INTEGER,
        outletConfigMaxPowerThresh     INTEGER,
        outletConfigMaxPDThresh        INTEGER,
        outletConfigAutoPingContFailTimes INTEGER,
        outletConfigAutoPingIntervalSec   INTEGER,
        outletConfigAutoPingRetryTimes    INTEGER,
        outletConfigAutoPingPowerUpDelaySec INTEGER,
        outletConfigAutoPingRemoteIPAddr    IpAddress,
        outletConfigAutoPingEnable     INTEGER,
        outletConfigAutoPingEnableReboot INTEGER
    }

outletConfigName OBJECT-TYPE
    SYNTAX DisplayString
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the name of the outlet.   
        If the station does not support this OID, we show n/a.
        string length: 0~48
        If the station is not available, it returns 'station N/A'.
        NOTE: Input string as /empty to set this object to NULL."
    ::= { outletConfigEntry 1 }

outletConfigConfirmationEn OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) , noauth(3), not-support(4) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the confirmation of the outlet.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 2 }

outletConfigOnDelayTime OBJECT-TYPE
    SYNTAX INTEGER (-1 | 0..999)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the ON delay time of the outlet.
        When this model does not support the OID, we show value -1.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 3 }

outletConfigOffDelayTime OBJECT-TYPE
    SYNTAX INTEGER (-1 | 0..999)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the OFF delay time of the outlet.
        When this model does not support the OID, we show value -1.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 4 }

outletConfigShutdownMethod OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), kill-the-power(1), wake-on-lan(2), after-ac-back(3), not-support(4) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the shutdown method of the outlet.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 5 }

outletConfigMAC OBJECT-TYPE
    SYNTAX MacAddress
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the MAC address of shutdown method.
        The value is hex format with length 12.
        If the station does not support this OID, it return '00-00-00-00-00-00'.
        If the station is not available, it returns '00-00-00-00-00-00'."
    ::= { outletConfigEntry 6 }

outletConfigLocalAccessLock OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), unlocked(1), locked(2), not-support(3) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set whether the local access of the outlet is locked by remote or not.
        If the station is not available, it returns value -3000000."
   ::= { outletConfigEntry 7 }

outletConfigMinCurThresh OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the outlet minimum electric current measurement threshold. 
        Example: range 0.0 ~16.0 represents 0~160
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 8 }

outletConfigMaxCurThresh OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the outlet maximum electric current measurement threshold. 
        Example: range 0.0 ~16.0 represents 0~160
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 9 }

outletConfigMinVolThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 900..2600)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the outlet minimum voltage measurement threshold. 
        Example: range 90.0 ~260.0 represents 900~2600
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 10 }

outletConfigMaxVolThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 900..2600)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the outlet maximum voltage measurement threshold. 
        Example: range 90.0 ~260.0 represents 900~2600
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 11 }

outletConfigMinPowerThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the outlet minimum power measurement threshold.
        Example: range 0.0 ~ 9999.9 represents 0~99999
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 12 }

outletConfigMaxPowerThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the outlet maximum power measurement threshold.
        Example: range 0.0 ~ 9999.9 represents 0~99999
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 13 }

outletConfigMaxPDThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..999990)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the outlet maximum power dissipation measurement threshold.
        Example: range 0.0 ~ 99999.0 represents 0~999990
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 14 }

outletConfigAutoPingContFailTimes OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..10)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the outlet auto-ping continuously-failed time to reset outlet.
        Example: range 0 ~ 5
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 15 }

outletConfigAutoPingIntervalSec OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..60)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the outlet auto-ping pinging interval in seconds.
        Example: range 10 ~ 600
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 16 }

outletConfigAutoPingRetryTimes OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..10)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the outlet auto-ping max retry times.
        Example: range 0 ~ 5
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 17 }

outletConfigAutoPingPowerUpDelaySec OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..60)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the outlet auto-ping first-ping-delay in seconds after outlet switches on.
        Example: range 10 ~ 600
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 18 }

outletConfigAutoPingRemoteIPAddr OBJECT-TYPE
    SYNTAX IpAddress
    MAX-ACCESS  read-write
    STATUS current
    DESCRIPTION
        "Outlet auto-ping destination IP address.
        If the station does not support this OID, it returns value '0.0.0.0'.
        If the station is not available, it returns '0.0.0.0'."
    ::= { outletConfigEntry 19 }

outletConfigAutoPingEnable OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), disable(1), enable(2) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the outlet auto-ping enable state.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 20 }

outletConfigAutoPingEnableReboot OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), not-support(-2000000), disable(1), enable(2) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the outlet auto-ping reboot enable state.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletConfigEntry 21 }
	
---------------------------------------------------------------------------------------------------
-- outletControlTable
---------------------------------------------------------------------------------------------------
outletControlTable OBJECT-TYPE
    SYNTAX SEQUENCE OF OutletControlEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Outlet control table."
    ::= { outlet 3 }

outletControlEntry OBJECT-TYPE
    SYNTAX OutletControlEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing outlet control info."
    INDEX { staId, outletId }
    ::= { outletControlTable 1 }
     
OutletControlEntry ::=
    SEQUENCE {
        outletControlOperation INTEGER
    }

outletControlOperation OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "This function is used for the outlet control.
        Set off(1) to turn off the outlet.
        Set on(2) to turn on the outlet.
        Set reboot(3) to reboot the outlet.
        pending(3), fault(5), noauth(6), not-suport(7), pop(8) can't be set.
        If the station is not available, it returns value -3000000."
    ::= { outletControlEntry 1 }

---------------------------------------------------------------------------------------------------
-- outletReadingTable
---------------------------------------------------------------------------------------------------
outletReadingTable OBJECT-TYPE
    SYNTAX SEQUENCE OF OutletReadingEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Outlet reading table."
    ::= { outlet 4 }

outletReadingEntry OBJECT-TYPE
    SYNTAX OutletReadingEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing outlet reading info."
    INDEX { staId, outletId }
    ::= { outletReadingTable 1 }
     
OutletReadingEntry ::=
    SEQUENCE {
        outletReadingCur    INTEGER,
        outletReadingVol    INTEGER,
        outletReadingPower  INTEGER,
        outletReadingPD     INTEGER,
        outletReadingPF     INTEGER
    }

outletReadingCur OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Outlet electric current value.
        This value indicates that 10,000 times.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletReadingEntry 1 }

outletReadingVol OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Outlet voltage value.
        This value indicates that 10,000 times.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletReadingEntry 2 } 

outletReadingPower OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Outlet power value.
        This value indicates that 10,000 times.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletReadingEntry 3 }   

outletReadingPD OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Outlet power dissipation value.
        This value indicates that 10,000 times.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletReadingEntry 4 }

outletReadingPF OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Outlet Power Factor value.
        This value indicates that 100 times.  
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletReadingEntry 5 }

---------------------------------------------------------------------------------------------------
-- outletAutoPingIpTable
---------------------------------------------------------------------------------------------------
outletAutoPingIpTable OBJECT-TYPE
    SYNTAX SEQUENCE OF OutletAutoPingIpEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Outlet auto-ping table."
    ::= { outlet 5 }
	
outletAutoPingIpEntry OBJECT-TYPE
    SYNTAX OutletAutoPingIpEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing outlet auto-ping ip info."
    INDEX { staId, outletId }
    ::= { outletAutoPingIpTable 1 }
	
OutletAutoPingIpEntry ::=
    SEQUENCE {
		outletConfigAutoPingRemoteIPType	InetAddressType,
        outletConfigAutoPingRemoteIP    	InetAddress
    }
	
outletConfigAutoPingRemoteIPType OBJECT-TYPE
    SYNTAX InetAddressType {ipv4(1), ipv6(2)}
    MAX-ACCESS  read-only
    STATUS current
    DESCRIPTION
        "Represents the type of the corresponding instance
            of outletConfigAutoPingRemoteIP object.
		If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { outletAutoPingIpEntry 1 }
	
outletConfigAutoPingRemoteIP OBJECT-TYPE
    SYNTAX InetAddress
    MAX-ACCESS  read-write
    STATUS current
    DESCRIPTION
        "Outlet auto-ping destination IP address.
        If the station does not support this OID, it returns value '0.0.0.0'.
        If the station is not available, it returns '0.0.0.0'."
    ::= { outletAutoPingIpEntry 2 }
	
---------------------------------------------------------------------------------------------------
-- lineStatusTable
---------------------------------------------------------------------------------------------------
lineStatusTable OBJECT-TYPE
    SYNTAX SEQUENCE OF LineStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Line status table."
    ::= { line 1 }

lineStatusEntry OBJECT-TYPE
    SYNTAX LineStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing line status info."
    INDEX { staId, lineId }
    ::= { lineStatusTable 1 }
     
LineStatusEntry ::=
    SEQUENCE {
        lineId             INTEGER,
        lineStatusRatedCur INTEGER
    }

lineId OBJECT-TYPE
    SYNTAX INTEGER (1..3)
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Line ID."
    ::= { lineStatusEntry 1 }

lineStatusRatedCur OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "The Max Line Current value. unit: (0.1mA)
        If the station is not available, it returns value -3000000."
    ::= { lineStatusEntry 2 }

---------------------------------------------------------------------------------------------------
-- lineConfigTable
---------------------------------------------------------------------------------------------------
lineConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF LineConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Line config table."
    ::= { line 2 }

lineConfigEntry OBJECT-TYPE
    SYNTAX LineConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing line config info."
    INDEX { staId, lineId }
    ::= { lineConfigTable 1 }
     
LineConfigEntry ::=
    SEQUENCE {
        lineConfigMinCurThresh   INTEGER,
        lineConfigMaxCurThresh   INTEGER,
        lineConfigMinVolThresh   INTEGER,
        lineConfigMaxVolThresh   INTEGER,
        lineConfigMinPowerThresh INTEGER,
        lineConfigMaxPowerThresh INTEGER
    }

lineConfigMinCurThresh OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the line Minimum current measurement threshold. 
        Example: range 0.0 ~16.0 represents 0~160
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { lineConfigEntry 1 }

lineConfigMaxCurThresh OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the line Maximum electric current measurement threshold. 
        Example: range 0.0 ~16.0 represents 0~160
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { lineConfigEntry 2 }

lineConfigMinVolThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 900..3800)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the line minimum voltage measurement threshold. 
        Example: range 90.0 ~380.0 represents 900~3800
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { lineConfigEntry 3 }
 
lineConfigMaxVolThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 900..3800)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the line maximum voltage measurement threshold. 
        Example: range 90.0 ~380.0 represents 900~3800
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { lineConfigEntry 4 }

lineConfigMinPowerThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the line minimum power measurement threshold.
        Example: range 0.0 ~ 9999.9 represents 0~99999
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { lineConfigEntry 5 }

lineConfigMaxPowerThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the line maximum power measurement threshold.
        Example: range 0.0 ~ 9999.9 represents 0~99999
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { lineConfigEntry 6 }
 
---------------------------------------------------------------------------------------------------
-- lineReadingTable
---------------------------------------------------------------------------------------------------
lineReadingTable OBJECT-TYPE
    SYNTAX SEQUENCE OF LineReadingEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Line reading table."
    ::= { line 3 }

lineReadingEntry OBJECT-TYPE
    SYNTAX LineReadingEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing line reading info."
    INDEX { staId, lineId }
    ::= { lineReadingTable 1 }
     
LineReadingEntry ::=
    SEQUENCE {
        lineReadingCur    INTEGER,
        lineReadingVol    INTEGER,
        lineReadingPower  INTEGER
    }

lineReadingCur OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Line current value.
        This value indicates that 10,000 times.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { lineReadingEntry 1 }

lineReadingVol OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Line voltage value.
        This value indicates that 10,000 times.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { lineReadingEntry 2 } 

lineReadingPower OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Line power value.
        This value indicates that 10,000 times.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { lineReadingEntry 3 }

---------------------------------------------------------------------------------------------------
-- neutralStatusTable
---------------------------------------------------------------------------------------------------
neutralStatusTable OBJECT-TYPE
    SYNTAX SEQUENCE OF NeutralStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Line reading table."
    ::= { line 4 }

neutralStatusEntry OBJECT-TYPE
    SYNTAX NeutralStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing line reading info."
    INDEX { staId }
    ::= { neutralStatusTable 1 }
     
NeutralStatusEntry ::=
    SEQUENCE {
        neutralStatusLeakageCur INTEGER
    }

neutralStatusLeakageCur OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no-detection(1), detection(2), not-support(3) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Neutral leakage current status.
        If the station is not available, it returns value -3000000."
    ::= { neutralStatusEntry 1 }
	
---------------------------------------------------------------------------------------------------
-- inletStatusTable
---------------------------------------------------------------------------------------------------
inletStatusTable OBJECT-TYPE
    SYNTAX SEQUENCE OF InletStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Inlet status table."
    ::= { inlet 1 }

inletStatusEntry OBJECT-TYPE
    SYNTAX InletStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing inlet status info."
    INDEX { staId, inletId }
    ::= { inletStatusTable 1 }
     
InletStatusEntry ::=
    SEQUENCE {
        inletId             INTEGER,
        inletStatusRatedCur INTEGER
    }

inletId OBJECT-TYPE
    SYNTAX INTEGER (1..3)
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Line ID."
    ::= { inletStatusEntry 1 }

inletStatusRatedCur OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "The Inlet Max Current value. unit: (0.1mA).
		If device is phase wye, then means L1 or L2 or L3 current.
		If device is phase delta, then means L1L2 or L2L3 or L3L1 current.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { inletStatusEntry 2 }

---------------------------------------------------------------------------------------------------
-- inletConfigTable
---------------------------------------------------------------------------------------------------
inletConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF InletConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Inlet config table."
    ::= { inlet 2 }

inletConfigEntry OBJECT-TYPE
    SYNTAX InletConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing inlet config info."
    INDEX { staId, inletId }
    ::= { inletConfigTable 1 }
     
InletConfigEntry ::=
    SEQUENCE {
        inletConfigMinCurThresh   INTEGER,
        inletConfigMaxCurThresh   INTEGER,
        inletConfigMinVolThresh   INTEGER,
        inletConfigMaxVolThresh   INTEGER,
        inletConfigMinPowerThresh INTEGER,
        inletConfigMaxPowerThresh INTEGER,
		inletConfigMaxPDThresh 	  INTEGER
    }

inletConfigMinCurThresh OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the inlet Minimum current measurement threshold. 
        Example: range 0.0 ~16.0 represents 0~160
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { inletConfigEntry 1 }

inletConfigMaxCurThresh OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the inlet Maximum electric current measurement threshold. 
        Example: range 0.0 ~16.0 represents 0~160
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { inletConfigEntry 2 }

inletConfigMinVolThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 900..3800)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the inlet minimum voltage measurement threshold. 
        Example: range 90.0 ~380.0 represents 900~3800
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { inletConfigEntry 3 }
 
inletConfigMaxVolThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 900..3800)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the inlet maximum voltage measurement threshold. 
        Example: range 90.0 ~380.0 represents 900~3800
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { inletConfigEntry 4 }

inletConfigMinPowerThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the inlet minimum power measurement threshold.
        Example: range 0.0 ~ 9999.9 represents 0~99999
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { inletConfigEntry 5 }

inletConfigMaxPowerThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..99999)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the inlet maximum power measurement threshold.
        Example: range 0.0 ~ 9999.9 represents 0~99999
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { inletConfigEntry 6 }
	
inletConfigMaxPDThresh OBJECT-TYPE
    SYNTAX INTEGER (-2000000 | -3000 | 0..999990)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the inlet maximum power dissipation measurement threshold.
        Example: range 0.0 ~ 99999.0 represents 0~999990
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { inletConfigEntry 7 }
 
---------------------------------------------------------------------------------------------------
-- inletReadingTable
---------------------------------------------------------------------------------------------------
inletReadingTable OBJECT-TYPE
    SYNTAX SEQUENCE OF InletReadingEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Inlet reading table."
    ::= { inlet 3 }

inletReadingEntry OBJECT-TYPE
    SYNTAX InletReadingEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing inlet reading info."
    INDEX { staId, inletId }
    ::= { inletReadingTable 1 }
     
InletReadingEntry ::=
    SEQUENCE {
        inletReadingCur    INTEGER,
        inletReadingVol    INTEGER,
        inletReadingPower  INTEGER,
		inletReadingPD     INTEGER
    }

inletReadingCur OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Inlet current value.
		If device is phase wye, then means L1 or L2 or L3 current.
		If device is phase delta, then means L1L2 or L2L3 or L3L1 current.
        This value indicates that 10,000 times.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { inletReadingEntry 1 }

inletReadingVol OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Inlet voltage value.
		If device is phase wye, then means L1 or L2 or L3 voltage.
		If device is phase delta, then means L1L2 or L2L3 or L3L1 voltage.
        This value indicates that 10,000 times.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { inletReadingEntry 2 } 

inletReadingPower OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Inlet power value.
		If device is phase wye, then means L1 or L2 or L3 power.
		If device is phase delta, then means L1L2 or L2L3 or L3L1 power.
        This value indicates that 10,000 times.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { inletReadingEntry 3 }
	
inletReadingPD OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
	"Inlet power value.
	If device is phase wye, then means L1 or L2 or L3 power dissipation.
	If device is phase delta, then means L1L2 or L2L3 or L3L1 power dissipation.
	This value indicates that 10,000 times.
	If the station does not support this OID, it returns value -2000000.
	If the station is not available, it returns value -3000000."
::= { inletReadingEntry 4 }

---------------------------------------------------------------------------------------------------
-- sensorConfigTable
---------------------------------------------------------------------------------------------------
sensorConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF SensorConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Sensor config table.
        Use port/addr as indexes to access sensor configurations."
    ::= { sensor 3 }

sensorConfigEntry OBJECT-TYPE
    SYNTAX SensorConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing sensor config info."
    INDEX { staId, sensorPort, sensorAddr }
    ::= { sensorConfigTable 1 }

SensorConfigEntry ::=
    SEQUENCE {
        sensorPort                 INTEGER,
        sensorAddr                 INTEGER,
        sensorConfigMinTempThresh  INTEGER,
        sensorConfigMaxTempThresh  INTEGER,
        sensorConfigMinHumThresh   INTEGER,
        sensorConfigMaxHumThresh   INTEGER,
        sensorConfigMinPressThresh INTEGER,
        sensorConfigMaxPressThresh INTEGER
    }

sensorPort OBJECT-TYPE
    SYNTAX INTEGER (1..4)
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Sensor Port Number."
    ::= { sensorConfigEntry 1 }

sensorAddr OBJECT-TYPE
    SYNTAX INTEGER (1..31)
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Sensor Address."
    ::= { sensorConfigEntry 2 }

sensorConfigMinTempThresh OBJECT-TYPE
    SYNTAX INTEGER (-3000 | -200..600)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set sensor minimum temperature measurement threshold.
        Example: range -20.0 ~ 60.0 represents -200~600
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { sensorConfigEntry 3 }

sensorConfigMaxTempThresh OBJECT-TYPE
    SYNTAX INTEGER (-3000 | -200..600)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set sensor maximum temperature measurement threshold.
        Example: range -20.0 ~ 60.0 represents -200~600
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { sensorConfigEntry 4 }

sensorConfigMinHumThresh OBJECT-TYPE
    SYNTAX INTEGER (-3000 | 100..950)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set sensor minimum humidity measurement threshold.
        Example: range 10.0 ~ 95.0 represents 100~950
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { sensorConfigEntry 5 }

sensorConfigMaxHumThresh OBJECT-TYPE
    SYNTAX INTEGER (-3000 | 100..950)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set sensor maximum humidity measurement threshold.
        Example: range 10.0 ~ 95.0 represents 100~950
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { sensorConfigEntry 6 }

sensorConfigMinPressThresh OBJECT-TYPE
    SYNTAX INTEGER (-3000 | -2500..2500)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set sensor minimum pressure measurement threshold.
        Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { sensorConfigEntry 7 }

sensorConfigMaxPressThresh OBJECT-TYPE
    SYNTAX INTEGER (-3000 | -2500..2500)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set sensor maximum pressure measurement threshold.
        Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
        NOTICE: Minimum threshold should be smaller than maximum threshold.
        Empty value: -3000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { sensorConfigEntry 8 }

---------------------------------------------------------------------------------------------------
-- sensorReadingTable
---------------------------------------------------------------------------------------------------
sensorReadingTable OBJECT-TYPE
    SYNTAX SEQUENCE OF SensorReadingEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Sensor reading table.
        Use port/addr as indexes to access sensor readings."
    ::= { sensor 4 }

sensorReadingEntry OBJECT-TYPE
    SYNTAX SensorReadingEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing sensor reading info."
    INDEX { staId, sensorPort, sensorAddr }
    ::= { sensorReadingTable 1 }

SensorReadingEntry ::=
    SEQUENCE {
        sensorReadingTemp  INTEGER,
        sensorReadingHum   INTEGER,
        sensorReadingPress INTEGER
    }

sensorReadingTemp OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Sensor's Temperature value.
        This value indicates that 1,000 times.
        If this measurement value is not available, it returns value -1000000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { sensorReadingEntry 1 }

sensorReadingHum OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Sensor's Humidity value.
        This value indicates that 1,000 times.
        If this measurement value is not available, it returns value -1000000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { sensorReadingEntry 2 }

sensorReadingPress OBJECT-TYPE
    SYNTAX INTEGER
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Sensor's Pressure value.
        This value indicates that 1,000 times.
        If this measurement value is not available, it returns value -1000000.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { sensorReadingEntry 3 }

---------------------------------------------------------------------------------------------------
-- dryContactStatusTable
---------------------------------------------------------------------------------------------------
dryContactStatusTable OBJECT-TYPE
    SYNTAX SEQUENCE OF DryContactStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Dry contact status table."
    ::= { dryContact 1 }

dryContactStatusEntry OBJECT-TYPE
    SYNTAX DryContactStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing dry contact status info."
    INDEX { staId, dryContactId }
    ::= { dryContactStatusTable 1 }
     
DryContactStatusEntry ::=
    SEQUENCE {
        dryContactId     INTEGER,
        dryContactStatus INTEGER
    }

dryContactId OBJECT-TYPE
    SYNTAX INTEGER (1..2)
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Dry contact ID."
    ::= { dryContactStatusEntry 1 } 
  
dryContactStatus OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), close(0), open(1), not-attached(2), not-support(10) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Display dry contact status.
        close(0) represents door close.
        open(1) represents door open.
        not-attached(2) represents door sensor don't attach to device.
        If the station is not available, it returns value -3000000."
    ::= { dryContactStatusEntry 2 }

---------------------------------------------------------------------------------------------------
-- dryContactConfigTable
---------------------------------------------------------------------------------------------------
dryContactConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF DryContactConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Dry contact config table."
    ::= { dryContact 2 }

dryContactConfigEntry OBJECT-TYPE
    SYNTAX DryContactConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing dry contact config info."
    INDEX { staId, dryContactId }
    ::= { dryContactConfigTable 1 }
     
DryContactConfigEntry ::=
    SEQUENCE {
        dryContactConfigType INTEGER
    }

dryContactConfigType OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), notinstalled(0), photo(1), inductiveproximity(2), reed(3), waterleakage(4), smoke(5), not-support(10) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set dry contact type.
        If the station is not available, it returns value -3000000."
    ::= { dryContactConfigEntry 1 }

---------------------------------------------------------------------------------------------------
-- netStatusTable
---------------------------------------------------------------------------------------------------
netStatusTable OBJECT-TYPE
    SYNTAX SEQUENCE OF NetStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Net status table."
    ::= { network 1 }

netStatusEntry OBJECT-TYPE
    SYNTAX NetStatusEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing net status info."
    INDEX { staId }
    ::= { netStatusTable 1 }
     
NetStatusEntry ::=
    SEQUENCE {
        netStatusMAC MacAddress
    }

netStatusMAC OBJECT-TYPE
    SYNTAX MacAddress
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Station MAC address.
        The value is hex format with length 12.
        If the station does not support this OID, it return '00-00-00-00-00-00'.
        If the station is not available, it returns '00-00-00-00-00-00'."
    ::= { netStatusEntry 1 }

---------------------------------------------------------------------------------------------------
-- httpConfigTable
---------------------------------------------------------------------------------------------------
httpConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF HttpConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "HTTP config table."
    ::= { network 2 }

httpConfigEntry OBJECT-TYPE
    SYNTAX HttpConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing HTTP config info."
    INDEX { staId }
    ::= { httpConfigTable 1 }
     
HttpConfigEntry ::=
    SEQUENCE {
        httpConfigHttpPort    INTEGER,
        httpConfigHttpsPort   INTEGER,
        httpConfigHttpsOnlyEn INTEGER
    }

httpConfigHttpPort OBJECT-TYPE
    SYNTAX INTEGER (1..65535)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the HTTP port of the station.
        If the station is not available, it returns value -3000000." 
    ::= { httpConfigEntry 1 }

httpConfigHttpsPort OBJECT-TYPE
    SYNTAX INTEGER (1..65535)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set the HTTPs port of the station.
        If the station is not available, it returns value -3000000."
    ::= { httpConfigEntry 2 }

httpConfigHttpsOnlyEn OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set whether to use HTTPS only or HTTP/HTTPS for the web page.
        If the station is not available, it returns value -3000000."
    ::= { httpConfigEntry 3 }

---------------------------------------------------------------------------------------------------
-- netConfigTable
---------------------------------------------------------------------------------------------------
netConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF NetConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Net config table."
    ::= { network 3 }

netConfigEntry OBJECT-TYPE
    SYNTAX NetConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing net config info."
    INDEX { staId, netCablePort }
    ::= { netConfigTable 1 }

NetConfigEntry ::=
    SEQUENCE {
        netCablePort            INTEGER,
        netConfigAutoIP         INTEGER,
        netConfigIPv4           IpAddress,
        netConfigSubMask        IpAddress,
        netConfigGateway        IpAddress,
        netConfigAutoDNS        INTEGER,
        netConfigPreferDNSIPv4  IpAddress,
        netConfigAlterDNSIPv4   IpAddress
    }

netCablePort OBJECT-TYPE
    SYNTAX INTEGER (1..2)
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Network Port Number."
    ::= { netConfigEntry 1 }

netConfigAutoIP  OBJECT-TYPE
    SYNTAX INTEGER { no(1), yes(2) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set IPv4 address automatically or not"
    ::= { netConfigEntry 2 }
netConfigIPv4  OBJECT-TYPE
    SYNTAX IpAddress
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set fixed IPv4 address"
    ::= { netConfigEntry 3 }
netConfigSubMask  OBJECT-TYPE
    SYNTAX IpAddress
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set subnet mask address"
    ::= { netConfigEntry 4 }
netConfigGateway  OBJECT-TYPE
    SYNTAX IpAddress
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set gateway address"
    ::= { netConfigEntry 5 }
netConfigAutoDNS  OBJECT-TYPE
    SYNTAX INTEGER { no(1), yes(2) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set DNS address automatically or not"
    ::= { netConfigEntry 6 }
netConfigPreferDNSIPv4  OBJECT-TYPE
    SYNTAX IpAddress
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set prefer DNS address"
    ::= { netConfigEntry 7 }
netConfigAlterDNSIPv4  OBJECT-TYPE
    SYNTAX IpAddress
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set alternate DNS address"
    ::= { netConfigEntry 8 }

---------------------------------------------------------------------------------------------------
-- trapConfigTable
---------------------------------------------------------------------------------------------------
trapConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF TrapConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Trap config table."
    ::= { trap 1 }

trapConfigEntry OBJECT-TYPE
    SYNTAX TrapConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing trap config info."
    INDEX { staId }
    ::= { trapConfigTable 1 }
     
TrapConfigEntry ::=
    SEQUENCE {
        trapConfigEn  INTEGER,
        trapConfigVer INTEGER
    }

trapConfigEn OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set whether this trap entry is enabled or not.
        You should set the username/auth-password/priv-password first, when choosing snmpv3.
        You should set the community string first, when choosing snmpv1/v2c.
        If the station is not available, it returns value -3000000."
    ::= { trapConfigEntry 1 }

trapConfigVer OBJECT-TYPE
 SYNTAX INTEGER { staNotAvailable(-3000000), v1(1), v2c(2), v3(3) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set SNMP trap version for sending trap.
        You should set the username/auth-password/priv-password first, when choosing snmpv3.
        You should set the community string first, when choosing snmpv1/v2c.
        If the station is not available, it returns value -3000000."
    ::= { trapConfigEntry 2 }

---------------------------------------------------------------------------------------------------
-- trapReceiverConfigTable
---------------------------------------------------------------------------------------------------
trapReceiverConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF TrapReceiverConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "SNMP agent trap setup table. If users want to use trap, 
        they must set enable trap, IP and community first."
    ::= { trap 2 }

trapReceiverConfigEntry OBJECT-TYPE
    SYNTAX TrapReceiverConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing trap receiver config info."
    INDEX { staId, trapReceiverConfigIdx }
    ::= { trapReceiverConfigTable 1 }
     
TrapReceiverConfigEntry ::=
    SEQUENCE {
        trapReceiverConfigIdx         INTEGER,
        trapReceiverConfigIp          IpAddress,
        trapReceiverConfigPort        INTEGER,
        trapReceiverConfigCommunity   DisplayString,
        trapReceiverConfigUsername    DisplayString,
        trapReceiverConfigAuthPwd     DisplayString,
        trapReceiverConfigPrivacyPwd  DisplayString
    }

trapReceiverConfigIdx OBJECT-TYPE
    SYNTAX INTEGER (1..2)
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Index of trap receiver."
    ::= { trapReceiverConfigEntry 1 }

trapReceiverConfigIp OBJECT-TYPE
    SYNTAX IpAddress
    MAX-ACCESS  read-write
    STATUS current
    DESCRIPTION
        "Trap receiver IP address.
        If the station does not support this OID, it returns value '0.0.0.0'.
        If the station is not available, it returns '0.0.0.0'."
    ::= { trapReceiverConfigEntry 2 }

trapReceiverConfigPort OBJECT-TYPE
 SYNTAX INTEGER (1..65535)
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "NMS trap port to be used by agent to send trap.
        If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { trapReceiverConfigEntry 3 }

trapReceiverConfigCommunity OBJECT-TYPE
    SYNTAX DisplayString (SIZE (0..20))
    MAX-ACCESS  read-write
    STATUS current
    DESCRIPTION
        "If use SNMPv1/v2c to receive trap should set this community string.
        MAX string length: 20
        If the station does not support this OID, it returns value 'not-support'.
        If the station is not available, it returns 'station N/A'.
        NOTE: Input string as /empty to set this object to NULL."
    ::= { trapReceiverConfigEntry 4 }

trapReceiverConfigUsername OBJECT-TYPE
    SYNTAX DisplayString (SIZE (0..20))
    MAX-ACCESS  read-write
    STATUS current
    DESCRIPTION
        "If use SNMPv3 to receive trap should set this username string.
        MAX string length: 20.
        If the station does not support this OID, it returns value 'not-support'.
        If the station is not available, it returns 'station N/A'.
        NOTE: Input string as /empty to set this object to NULL."
    ::= { trapReceiverConfigEntry 5 }

trapReceiverConfigAuthPwd OBJECT-TYPE
    SYNTAX DisplayString (SIZE (8..20))
    MAX-ACCESS  read-write
    STATUS current
    DESCRIPTION
        "If use SNMPv3 to receive trap should set this auth password string.
        MAX string length: 20
        If the station does not support this OID, it returns value 'not-support'.
        If the station is not available, it returns 'station N/A'.
        NOTE: Input string as /empty to set this object to NULL."
    ::= { trapReceiverConfigEntry 6 }

trapReceiverConfigPrivacyPwd OBJECT-TYPE
    SYNTAX DisplayString (SIZE (8..20))
    MAX-ACCESS  read-write
    STATUS current
    DESCRIPTION
        "If use SNMPv3 to receive trap should set this privacy password string.
        MAX string length: 20
        If the station does not support this OID, it returns value 'not-support'.
        If the station is not available, it returns 'station N/A'.
        NOTE: Input string as /empty to set this object to NULL."
    ::= { trapReceiverConfigEntry 7 }
	
---------------------------------------------------------------------------------------------------
-- trapReceiverIpTable
---------------------------------------------------------------------------------------------------
trapReceiverIpTable OBJECT-TYPE
    SYNTAX SEQUENCE OF TrapReceiverIpEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Trap Receiver Ip table."
    ::= { trap 3 }
	
trapReceiverIpEntry OBJECT-TYPE
    SYNTAX TrapReceiverIpEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing trap receiver ip info."
    INDEX { staId, trapReceiverIpIdx }
    ::= { trapReceiverIpTable 1 }
	
TrapReceiverIpEntry ::=
    SEQUENCE {
		trapReceiverIpIdx       INTEGER,
		trapReceiverIpType		InetAddressType,
        trapReceiverIp    		InetAddress
    }

trapReceiverIpIdx OBJECT-TYPE
    SYNTAX INTEGER (1..2)
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Index of trap receiver."
    ::= { trapReceiverIpEntry 1 }

trapReceiverIpType OBJECT-TYPE
    SYNTAX InetAddressType {ipv4(1), ipv6(2)}
    MAX-ACCESS  read-only
    STATUS current
    DESCRIPTION
        "Represents the type of the corresponding instance
            of trapReceiverIp object.
		If the station does not support this OID, it returns value -2000000.
        If the station is not available, it returns value -3000000."
    ::= { trapReceiverIpEntry 2 }
	
trapReceiverIp OBJECT-TYPE
    SYNTAX InetAddress
    MAX-ACCESS  read-write
    STATUS current
    DESCRIPTION
        "Outlet auto-ping destination IP address.
        If the station does not support this OID, it returns value '0.0.0.0'.
        If the station is not available, it returns '0.0.0.0'."
    ::= { trapReceiverIpEntry 3 }

---------------------------------------------------------------------------------------------------
-- trapNotifConfigTable
---------------------------------------------------------------------------------------------------
trapNotifConfigTable OBJECT-TYPE
    SYNTAX SEQUENCE OF TrapNotifConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Trap notification config table."
    ::= { trapNotification 1 }

trapNotifConfigEntry OBJECT-TYPE
    SYNTAX TrapNotifConfigEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION
        "Single entry containing trap notification config info."
    INDEX { staId }
    ::= { trapNotifConfigTable 1 }
     
TrapNotifConfigEntry ::=
    SEQUENCE {
        trapNotifConfigEn INTEGER
    }

trapNotifConfigEn OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), no(1), yes(2) }
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Display or set whether this trap entry is enabled or not.
        You should set the username/auth-password/priv-password first, when choosing snmpv3.
        You should set the community string first, when choosing snmpv1/v2c.
        If the station is not available, it returns value -3000000."
    ::= { trapNotifConfigEntry 1 }

---------------------------------------------------------------------------------------------------
-- trapNotifAlarmTable
---------------------------------------------------------------------------------------------------
trapNotifAlarmTable OBJECT-TYPE
    SYNTAX SEQUENCE OF TrapNotifAlarmEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION "Trap notification alarm table."
    ::= { trapNotification 2 }

trapNotifAlarmEntry OBJECT-TYPE
    SYNTAX TrapNotifAlarmEntry
    MAX-ACCESS not-accessible
    STATUS current
    DESCRIPTION "Single entry containing trap notification alarm info."
    INDEX { staId }
    ::= { trapNotifAlarmTable 1 }
     
TrapNotifAlarmEntry ::=
    SEQUENCE {
        trapNotifAlarmBreakerStatus INTEGER,
        trapNotifAlarmCurrentStatus INTEGER,
        trapNotifAlarmVoltageStatus INTEGER,
        trapNotifAlarmPowerStatus INTEGER,
        trapNotifAlarmSensorStatus INTEGER
    }

trapNotifAlarmBreakerStatus OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Station breaker alarm status.
        If the station is not available, it returns value -3000000."
    ::= { trapNotifAlarmEntry 1 }

trapNotifAlarmCurrentStatus OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Station current alarm status.
        If the station is not available, it returns value -3000000."
    ::= { trapNotifAlarmEntry 2 }

trapNotifAlarmVoltageStatus OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Station voltage alarm status.
        If the station is not available, it returns value -3000000."
    ::= { trapNotifAlarmEntry 3 }

trapNotifAlarmPowerStatus OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Station power alarm status.
        If the station is not available, it returns value -3000000."
    ::= { trapNotifAlarmEntry 4 }

trapNotifAlarmSensorStatus OBJECT-TYPE
    SYNTAX INTEGER { staNotAvailable(-3000000), normal(0), alarm(1) }
    MAX-ACCESS read-only
    STATUS current
    DESCRIPTION
        "Station sensor alarm status.
        If the station is not available, it returns value -3000000."
    ::= { trapNotifAlarmEntry 5 }

---------------------------------------------------------------------------------------------------
-- trapNotifEvent
---------------------------------------------------------------------------------------------------
trapNotifEvent NOTIFICATION-TYPE
    STATUS current
    DESCRIPTION "Display trap notification alarm status."
    ::= { trapNotification 3 }
---------------------------------------------------------------------------------------------------
-- deviceLock
---------------------------------------------------------------------------------------------------
staCommunityLock OBJECT-TYPE
    SYNTAX DisplayString
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Change SNMPV1 or SNMPV2 community for California passes law.
		Please follow the format as readcommunity||writecommunity"
    ::= { deviceLock 1 }
staPasswordLock OBJECT-TYPE
    SYNTAX DisplayString
    MAX-ACCESS read-write
    STATUS current
    DESCRIPTION
        "Change SNMPV3 password for California passes law.
		Please follow the format as authpassword||privpassword"
    ::= { deviceLock 2 }

END